# AGRINOVO-ULM-110: Explosion-Proof Ultrasonic Level Meter (Liquids, 5 to 20 m, Hazardous Area)

Agrinovo technical datasheet, revision 1.2 (October 2026).
PDF version: https://agrinovo.io/datasheets/sensors/AGRINOVO-ULM-110_Datasheet.pdf

## 1. Overview

The AGRINOVO-ULM-110 is the hazardous-area variant of the AGRINOVO-ULM-100 ultrasonic level meter. It carries Ex d IIC T6 Gb (flameproof) and Ex ib IIB T6 Gb (intrinsic safety) certifications, allowing deployment in fuel storage, solvent tanks, and other Zone 1 / Zone 2 liquid-handling environments.

Electrical performance, measurement principle, output options, and Modbus protocol are identical to the AGRINOVO-ULM-100. The differences are mechanical: a heavier explosion-proof housing, an upgraded display protection rating (IP67), and an optional stainless steel probe (IP68).

### Key Features

- Ex d IIC T6 Gb (flameproof)
- Ex ib IIB T6 Gb (intrinsic safety)
- Selectable range: 5 / 10 / 15 / 20 m
- 4-20 mA (2-wire or 4-wire) output
- RS485 Modbus-RTU communication
- Up to 2 programmable relays
- Display IP67, probe IP68
- Stainless steel probe option
- 24 VDC standard, 220 VAC optional
- Anti-corrosion probe option (PVDF / PTFE)
- LCD display with menu keypad
- Field-configurable from front panel

### Applications

- Fuel and lubricant storage tanks
- Solvent, alcohol, and condensate vessels
- Process tanks in petrochemical, paint, and coating facilities
- Wastewater lift stations and digesters in classified zones
- Any classified-area liquid level measurement where the AGRINOVO-ULM-100 housing is not suitable

## 2. Specifications

### Measurement

| Parameter | Specification |
|:----------|:--------------|
| **Measuring Range** | 5 m / 10 m / 15 m / 20 m (per probe variant) |
| **Accuracy** | 0.5% to 1.0% of measured range |
| **Resolution** | 3 mm or 0.1% of range |
| **Blind Zone** | 0.3 m (5 m range), 0.4 m (10 m), 0.6 m (15 m), 0.8 m (20 m) |
| **Measurement Modes** | Level (default) or Distance |
| **Application** | Liquids (water, fuels, solvents, non-aggressive process media) |
| **Temperature Compensation** | Automatic, internal sensor |

### Electrical

| Parameter | Specification |
|:----------|:--------------|
| **Power Supply** | 24 VDC standard, 220 VAC +15% / 50 Hz optional |
| **Analog Output** | 4-20 mA, 2-wire (250 Ω max load) or 4-wire (510 Ω max load) |
| **Digital Output** | RS485 Modbus-RTU |
| **Relay Output** | Optional 2 × SPDT, AC 250 V / 8 A or DC 30 V / 5 A, programmable |
| **Cable Entry** | M20×1.5 |

### Mechanical and Environmental

| Parameter | Specification |
|:----------|:--------------|
| **Display** | LCD with keypad |
| **Housing** | Die-cast aluminium dual chamber (IP67) or stainless steel (IP68) |
| **Protection Grade** | Display IP67, Probe IP68 |
| **Probe Material** | Standard polymer; PVDF or PTFE optional for corrosive media |
| **Process Connection** | Thread G1½, G2, M78×2, or flange DN50 / DN65 / DN80 / DN100 |
| **Process Pressure** | ≤0.3 MPa (3 bar) |
| **Process Temperature (probe)** | -20°C to +80°C |
| **Operating Temperature (display)** | -20°C to +60°C |

### Hazardous Area Classification

| Code | Meaning |
|:-----|:--------|
| **Ex d IIC T6 Gb** | Flameproof enclosure, Group IIC (hydrogen, acetylene), Temperature Class T6 (≤85°C surface), Equipment Protection Level Gb (Zone 1) |
| **Ex ib IIB T6 Gb** | Intrinsic safety, Group IIB (ethylene, town gas), Temperature Class T6, EPL Gb (Zone 1) |

## 3. Measurement Modes

The meter supports two output modes, selectable from the front panel or via Modbus.

### Level Mode (default)

4-20 mA output is proportional to liquid level (height of material above tank bottom).

### Distance Mode

4-20 mA output is proportional to distance from probe face to liquid surface (empty height).

## 4. Dimensions

### Explosion-Proof Housing (G2 Thread, 10 m to 20 m)

| Parameter | Value |
|:----------|:------|
| Housing diameter | 97 mm |
| Total height (housing + probe) | 269 mm |
| Probe length | 70 mm |
| Probe outer diameter | 52 mm |
| Process thread (G2 variant) | G2 |

The G1½ (5 m), M78×2 (15 m), and M78×2 (20 m) variants share the same explosion-proof head with different probe mountings. Contact Agrinovo for full dimensions per variant.

## 5. Installation

### Hazardous Area Compliance

Installation in a classified area must follow IEC 60079-14 and applicable local code. Cable glands, junction boxes, and conduit seals must be certified to the same EPL or higher as the meter.

### Position Selection

Install the meter perpendicular to the liquid surface. The space between the probe emitting face and the maximum liquid level must remain greater than the blind zone (see specifications table).

Avoid placement directly above fill streams, agitators, internal pipes, or weld seams. Any object within the beam path near the probe causes a strong false echo and corrupts the reading.

### Flat-Top Tank with Connecting Pipe

When a short connecting pipe (nozzle) is used, the pipe length must not exceed 60 mm and the inner diameter must be at least 100 mm. The probe emitting face must protrude at least 3 cm below the underside of the flange.

### Direct Flange Mount

The cleanest installation is direct mounting on the flat tank top without any connecting pipe. The probe emitting face sits below the datum plane and the full sensor range is usable above the blind zone.

### Open Container Mount

Use an installation bracket and maintain the minimum wall distance for the selected range.

| Range | Min. Distance to Wall |
|:------|:---------------------|
| 5 m | 0.5 m |
| 10 m | 1.0 m |
| 15 m | 1.5 m |
| 20 m | 2.5 m |

### Notes

- Ultrasonic transmission requires a gaseous medium between the probe and the liquid surface. **Vacuum vessels are not suitable.**
- When installing by thread, the probe must not be in direct contact with the metal bracket. Use the supplied rubber rings to isolate it.
- Mount the probe at 1/2 or 2/3 of the tank-top radius on arch-roof tanks to avoid lens-focused false echoes.

## 6. Electrical Connections

> Caution: AC power must only be connected to the AC terminals. Connecting AC to signal terminals will destroy the meter. The 485 and 4-20 mA output terminals must not be short-circuited.

> Hazardous area: do not open the enclosure when energised. Wait at least 5 minutes after power removal before opening.

### 6.1 Four-Wire Terminal Layout

### 6.2 Four-Wire Wiring Diagram

| Terminal | Signal | Function |
|:---------|:-------|:---------|
| 1, 2 | 24 VDC+ / 24 VDC- | Power supply |
| 3, 4 | mA+ / mA- | 4-20 mA current output |
| 5, 6 | 485A / 485B | RS485 Modbus communication |
| 7, 8 | RL2 / COM | Programmable relay 2 |
| 8, 9 | COM / RL1 | Programmable relay 1 |

### 6.3 Two-Wire Terminal Layout

### 6.4 Two-Wire Wiring (4-20 mA loop powered)

| Terminal | Signal | Function |
|:---------|:-------|:---------|
| 1 | 24 VDC+ | Loop supply + |
| 2 | 24 VDC- | Loop supply / 4-20 mA return |
| 3 | GND | Earth ground |

### 6.5 Grounding and Anti-Interference

- The meter must be grounded independently. Do not share grounding with frequency converters, motor drives, or panel boxes.
- Signal cables must not share a tray with power cables. Run signal cables in a separate metal conduit, or keep at least 1 m of separation.
- When the meter is powered alongside a VFD or motor, fit an isolation transformer on the supply side and a signal isolator on the analog output.

## 7. RS485 Modbus Communication

### Communication Settings

| Parameter | Value |
|:----------|:------|
| **Protocol** | Modbus-RTU |
| **Physical Layer** | RS485, half-duplex |
| **Frame** | 10 bits (1 start, 8 data, 1 stop, no parity) |
| **Baud Rate** | 2400 / 4800 / 9600 (default) / 19200 |
| **Default Slave Address** | 0x01 |
| **Address Range** | 0x01 to 0xFE |
| **Byte Order** | Big-endian (higher byte first) |
| **CRC** | CRC16 Modbus (low byte first) |

### Function Codes

- **0x03** Read holding registers
- **0x06** Write single register
- **0x10** Write multiple registers

### Register Map

Registers are partitioned into three areas. A single Modbus transaction must stay within one area.

| Area | Range | Access |
|:-----|:------|:-------|
| 1 | 0x0000 to 0x0021 | Read only |
| 2 | 0x0022 to 0x005B | Read / write |
| 3 | 0x005C to 0x006B | Read / write |

**Measurement registers (Area 1, function 0x03)**

| Address | Description | Format |
|:--------|:------------|:-------|
| 0x0000 | Instantaneous distance or level | UINT16, cm |
| 0x0001 | Instantaneous analog output | UINT16, raw |
| 0x0002 | Internal temperature | UINT16 |

The measurement register returns whichever quantity (distance or level) corresponds to the active measurement mode. The top bit of the high byte is the sign flag: 0 = positive, 1 = negative.

**Range and alarm registers (Area 2, function 0x03 / 0x10)**

| Address | Description | Unit |
|:--------|:------------|:-----|
| 0x0022 / 0x0023 | Alarm 1 value / Alarm 1 return difference | as configured |
| 0x0024 / 0x0025 | Alarm 2 value / Alarm 2 return difference | as configured |
| 0x0026 / 0x0027 | Alarm 3 value / Alarm 3 return difference | as configured |
| 0x0028 / 0x0029 | Alarm 4 value / Alarm 4 return difference | as configured |
| 0x002A | Reference zero point | as configured |
| 0x002B | Range high point (20 mA) | as configured |
| 0x002C | Range low point (4 mA) | as configured |
| 0x002D | Current setpoint (wave-loss output) | mA × 1000 |
| 0x002E | Blind zone | as configured |

**Configuration registers (Area 3, function 0x03 / 0x10)**

| Address | High Byte | Low Byte |
|:--------|:----------|:---------|
| 0x005C | Alarm 1 mode | Alarm 2 mode |
| 0x005D | Alarm 3 mode | Alarm 4 mode |
| 0x005E | Measurement mode | Unit option |
| 0x005F | Algorithm option | Safe-level mode |
| 0x0060 | Probe type | Response speed |
| 0x0061 | Factory reset | System reset |
| 0x0062 | Baud rate | Working mode |
| 0x006B | Sensor type character | Instrument address (read only) |

### Encoded Values

| Field | Values |
|:------|:-------|
| Measurement mode | 0 = Distance, 1 = Level |
| Unit option | 0 = mm, 1 = cm, 2 = m |
| Alarm mode | 0 = Off, 1 = Low-level alarm, 2 = High-level alarm |
| Safe level (wave loss) | 0x00 = Hold last, 0x55 = Output min, 0xAA = Output max, 0xA5 = Output set value |
| Response speed | 0 = Slow, 1 = Medium, 2 = Fast |
| Baud rate | 0 = 2400, 1 = 4800, 2 = 9600, 3 = 19200 |
| Working mode | 0 = Auto-report, 1 = Inquiry |

### Reading the Measured Value

**Example: read measurement from address 0x01**

```
Request:  01 03 00 00 00 01 84 0A
Response: 01 03 02 00 10 B9 88
```

| Field | Bytes | Value |
|:------|:------|:------|
| Raw register | 0x00 0x10 | 16 |
| Sign bit | 0 | Positive |
| Unit | cm | 16 cm |
| Result | | **0.16 m** |

**Example: negative reading (-0.16 m)**

```
Response: 01 03 02 80 10 D8 48
```

The high byte 0x80 has its top bit set (sign = negative); the magnitude is 0x0010 = 16 cm.

### Exception Codes

| Code | Meaning |
|:-----|:--------|
| 0x01 | Illegal function code |
| 0x02 | Illegal data address |
| 0x03 | Illegal data value |
| 0x04 | CRC16 check error |
| 0x05 | Receive correctly |
| 0x06 | Receive error |
| 0x07 | Parameter error |

## 8. Configuration Reference

### Range Setup

| Parameter | Description | Default |
|:----------|:------------|:--------|
| **Bottom Distance** | Reference zero point. Distance from probe face to tank bottom in level mode. | Maximum range |
| **Range Low (4 mA)** | Measurement value mapped to 4 mA output. | 0 |
| **Range High (20 mA)** | Measurement value mapped to 20 mA output. | Maximum range |
| **Display Unit** | m / cm / mm | m |

### Response and Damping

| Setting | Effect |
|:--------|:-------|
| Slow | High noise immunity, slowest tracking |
| Medium | Balanced (factory default) |
| Fast | Lowest latency, lower noise immunity |

### Wave-Loss Behaviour

When echo is lost (turbulent surface, foam, beam blockage), the output follows the safe-level setting:

- **Hold** (default): retains the last valid value, current output unchanged
- **Min**: forces 4 mA
- **Max**: forces 20 mA
- **Set value**: forces a user-defined current between 3.6 mA and 22 mA

### Relay Alarm Configuration (per relay)

| Parameter | Range |
|:----------|:------|
| Mode | Off / Low alarm / High alarm |
| Trigger value | meters |
| Return difference (hysteresis) | meters |

A single relay can control a complete pump cycle. To drain a tank between 1 m (stop) and 5 m (start): High-level alarm mode, value = 5.00 m, return difference = 4.00 m.

### Parameter Lock

Default unlock password is 25. The user may change the password at any time.

## 9. Application Notes

### Signal Attenuation Budget

Real-world conditions reduce echo strength. Choose a meter range with margin equal to the sum of expected attenuations:

| Condition | Attenuation |
|:----------|:------------|
| Light surface ripple | 5 to 10 dB |
| Heavy surface fluctuation, agitator running | 10 to 20 dB |
| Light vapour / mist | 5 to 10 dB |
| Heavy vapour / steam | 10 to 20 dB |
| Probe vs medium temperature difference ≤40°C | 5 to 10 dB |
| Probe vs medium temperature difference ≤80°C | 10 to 20 dB |

For each 10 dB of attenuation, multiply the required range by 1×; for combined attenuation totalling 15 to 40 dB, choose a meter at least 3× the actual maximum measured distance.

### Drainage Wells and Common Wells

Narrow wellheads require a measuring casing or connecting pipe. **Adding a pipe enlarges the blind zone by 50 to 100%.** For a 0.5 m native blind zone, expect 1.0 m once the casing is fitted.

Casing inner diameter must be ≥150 mm for measuring ranges up to 4 m. The inner wall must be smooth (PVC or PE works) and free of internal joints.

### When to Choose ULM-110 Over ULM-100

| Condition | Choose |
|:----------|:-------|
| Non-classified area, ordinary process liquid | AGRINOVO-ULM-100 |
| Zone 1 or Zone 2 hazardous area | AGRINOVO-ULM-110 |
| Flammable liquid (fuel, solvent, condensate) | AGRINOVO-ULM-110 |
| Stainless steel housing required (washdown, marine, sterile) | AGRINOVO-ULM-110 |
| IP67 display required (heavy washdown) | AGRINOVO-ULM-110 |

## 10. Ordering Configuration

The model number is built from the following fields. Contact Agrinovo to confirm a configuration before order.

| Field | Options |
|:------|:--------|
| Sensor type | Standard / Anti-corrosion |
| Housing | Die-cast aluminium dual chamber (IP67), stainless steel (IP68) |
| Probe mounting and range | G1½ 5 m / G2 10 m / M78×2 15 m or 20 m |
| Power supply | 220 VAC / 24 VDC / custom |
| Output mode | 4-20 mA 2-wire / 4-20 mA 4-wire / Modbus only / 4-20 mA + Modbus |
| Relay | None / 1 relay / 2 relays |
| Process connection | Thread (G1½, G2, M78×2) or flange (DN50, DN65, DN80, DN100) |

## 11. Fault Handling

| Symptom | Likely Cause | Action |
|:--------|:-------------|:-------|
| Meter does not power on | Power supply not connected | Inspect supply wiring |
| Display blank | Wiring loose between LCD and main board, or LCD damaged | De-energise (wait 5 min in classified area), re-seat the wiring; return for service if persistent |
| Output frozen, trumpet icon static | Measured surface beyond range, heavy disturbance, foam, or probe out of plumb | Select a larger range, allow medium to settle, re-aim probe perpendicular to surface, raise probe height, check for blockage in blind zone |
| Erratic readings | Strong nearby electromagnetic source (VFD, motor) | Verify grounding, add isolation transformer and signal isolator, separate signal and power cables |

## Revision History

| Rev | Date | Changes |
|:----|:-----|:--------|
| 1.0 | June 2026 | Initial release |
| 1.1 | August 2026 | Layout revision |
| 1.2 | October 2026 | New layout; corrected Modbus example CRC values |

## Contact

Agrinovo, https://agrinovo.io/products, contact@agrinovo.io, +972 54 688 8148 (direct / WhatsApp).
Specifications subject to change without notice.